6-27
6
Parameter description
6. Parameter description
Parameter
No.
Parameter name
Setting range
[Default value]
Description
FC-23
Communication
parity
non, odd, EvEn
[non]
Sets the parity f used to communicate with the PC
(TOP software for RD series).
Setting Description
non Communication parity: none
odd Communication parity: odd
EvEn Communication parity: even
After this parameter is changed, turn power off and
then back on to enable the change. Otherwise, a
malfunction will occur.
FC-24
Communication
stop bit
1, 2
[2]
Sets the stop bit used to communicate with the PC
(TOP software for RD series).
FC-30
Monitor output 1
function
nrF,
nFb, iFb,
tqr, nEr, PEr,
PFq, brd
[nFb]
Sets the data items to be output as the monitor
outputs 1 and 2 as shown in the table below. "yes"
indicates that the corresponding value is output,
and "no" indicates that 0V is output. The data items
shown in the "3V output value" column are available
when the monitor output gains 1 and 2 are 100.0.
Setting Data item
3.0V
output
value
Control mode
Position
Speed
Torque
nFb
Speed
detection
value
Maximum
speed
yes yes yes
tqr
Torque
command
value
Maximum
torque
yes yes yes
nrF
Speed
command
value
Maximum
speed
yes yes no
nEr
Speed
deviation
Maximum
speed
yes yes no
PEr
Position
deviation
Five
motor
rotations
yes no no
iFb
Current
value
Maximum
current
yes yes yes
PFq
Command
pulse
frequency
Maximum
speed
yes no no
brd
Regenerative
braking
resistor duty
ratio
Trip
level
(FA-08)
yes yes yes
Note: When an alarm has tripped, 0V is output from
all data items except the speed detection
value. However, if a position sensor error (E39)
occurs then the speed detection value is no
longer fixed.
FC-33
Monitor output 2
function
nrF,
nFb, iFb,
tqr, nEr, PEr,
PFq, brd
[tqr]
FC-31
Monitor output 1
polarity
SiGn, AbS
[SiGn]
This parameter specifies whether to output data
from monitor outputs 1 and 2 in a range of 0 to ±3.0V
or 0 to 3.0V.
Setting Description
SiGn 0 to ±3.0V
(Note)
AbS 0 to 3.0V
Note: The output is positive only when FC-30 and
FC-33 are set to "PFq" or "brd".
FC-34
Monitor output 2
polarity